Monocrystalline Silicon Pressure Transmitter Calibration Procedure Explained: A Full-Process Guide from Preparation to Fault Diagnosis
In modern industrial automation, monocrystalline silicon pressure transmitters have become core components of process control due to their high accuracy, strong stability, and excellent environmental adaptability. Especially in demanding applications such as ironmaking blast furnaces, chemical reactors, and power systems, regular calibration and timely fault diagnosis are directly related to production safety and efficiency. Nexisense monocrystalline silicon series products support intelligent HART communication, making calibration operations simple and reliable. Based on standard industrial specifications and real-world cases, this article systematically explains calibration procedures, common troubleshooting methods, and diagnostic experience in blast furnace applications, helping field engineers master practical skills and improve equipment management levels.
Safety and Preparation Before Calibration
Calibrating a monocrystalline silicon pressure transmitter is not a simple test, but a comprehensive operation involving high pressure, electrical, and process safety. Any negligence may result in equipment damage or safety accidents.
First, obtain the appropriate Work Permit, notify on-site operators and shift engineers, and place the relevant system in an “ON” state or safe mode. Wear complete personal protective equipment (PPE), including safety glasses, gloves, and anti-static clothing.
Prepare the necessary tools:
High-accuracy pressure calibrator (range greater than the transmitter; pneumatic type for low range, hydraulic type for high range).
HART communicator (such as HART 375 or compatible devices).
Multimeter (for 4–20 mA signal monitoring).
Connection accessories (such as 1/4" NPT fittings, hoses, unions).
Leak detection fluid (such as soapy water) and cleaning media.
Confirm environmental conditions: stable temperature and reliable power supply (24 VDC). Read the Nexisense product manual, verify range, accuracy, and output protocol, and ensure the calibrator accuracy is better than the transmitter (at least ±0.05% FS).
Standard Calibration Procedure Steps
Nexisense monocrystalline silicon transmitters adopt digital compensation technology, and calibration is mainly performed via HART. The following is the standard on-site procedure:
1. Process Isolation and Depressurization
Close the main process isolation valve (primary valve) to isolate the transmitter from the process medium. Open the vent and equalizing valves on the manifold to equalize the pressure on both sides of the transmitter to atmospheric pressure. Open the vent plug and confirm that there is no residual pressure (display close to zero).
2. Equipment Connection
Use appropriate fittings to connect the calibrator to the manifold vent port, ensuring the vent valve is open. Connect the HART communication cable to the transmitter signal terminals according to the wiring diagram. Connect a multimeter in series in the loop to monitor current output.
3. Zero Adjustment (Zero Trim)
Apply zero pressure (atmospheric pressure for gauge type; vacuum reference required for absolute type). Enter the menu via the HART communicator, select zero trim, and confirm the output is 4.000 mA. Execute the adjustment and repeat verification to ensure stability.
4. Span Adjustment and Linearity Verification (Span Trim)
Apply full-scale pressure (100%), input the actual value, and perform span trim via HART. Apply 25%, 50%, and 75% pressure points sequentially, and record the output and theoretical deviation (should be < ±0.075% FS). If out of tolerance, repeat zero/span adjustment. Check hysteresis and repeatability: the output difference at the same point during pressure increase/decrease should be minimal.
5. Removal and Restoration
Remove the calibrator and flush the pipeline (with water or air, avoiding hydraulic oil entering the transmitter). Close the vent plug and isolate the vent valve. Slowly open the main isolation valve and manifold valves to prevent water hammer from damaging the diaphragm. Confirm normal transmitter indication and verify consistency with DCS/PLC readings.
6. Record and Report
Fill out the calibration report, including before-and-after data, error calculations, environmental parameters, and signatures. Annual calibration is recommended; for critical applications such as blast furnaces, shorten the interval to six months.
Throughout the process, operate slowly to avoid impact. Nexisense products have built-in diagnostic functions and can monitor drift warnings via HART.
General Troubleshooting Methods
When a fault occurs, systematic inspection from measurement, circuitry, and field aspects can quickly locate the problem.
Measurement Section Inspection
Remove the flange and inspect the isolation diaphragm: deformation, damage, or oil leakage indicates sensor core failure and requires replacement. Remove the compensation board (without removing the sensing element) and measure the insulation resistance between pins and housing (<100 V): it should be >100 MΩ. Pressurize to the upper limit, then close the air source and observe the output: a drop indicates leakage, which can be located using soapy water.
Circuit Section Inspection
No output: check power supply voltage, polarity, and wiring; after elimination, inspect for amplifier board component damage or poor connector contact. Compare voltage measurement points with a normal instrument to locate faults and replace the faulty board (anti-static operation required).
Output too high/low with no response: check the oscillation circuit (high-frequency transformer peak value 25–35 Vp-p, 32 kHz) and operational amplifier status. Replacing the amplifier board is a common solution.
After confirming line faults, contact Nexisense to replace boards and ensure reliability.
Field Section Inspection
Primary element blockage, improper pressure tapping point, impulse line leakage/blockage, residual gas/liquid, and sediment dead zones. Wiring errors, power supply abnormalities, and poor indicator head contact. Installation not compliant with specifications: non-vertical installation or environmental limits exceeded.
Troubleshooting sequence: field → circuit → measurement.
Fault Diagnosis Cases in Blast Furnace Applications
In ironmaking blast furnaces, monocrystalline silicon transmitters monitor parameters such as furnace top pressure, hot blast pressure, and compressed air. The following analyses are based on actual cases.
Case: Abnormally Low Furnace Top Pressure
Phenomenon: Monitoring shows one redundant transmitter is 50 kPa lower. Analysis: First simulate output with a standard signal to confirm transmitter failure. Check zero drift, surge protector damage, and pressure tapping blockage. Treatment: Adjust zero; replace surge protector; clean tapping port gasket; adjust current with a calibrator. If ineffective, replace the transmitter.
Case: High Compressed Air Pressure Indication
Phenomenon: Output current is high. Analysis: Zero drift or water accumulation in impulse lines (compressed air contains moisture and easily condenses). Treatment: Open drain valve to remove water and enhance insulation; fault eliminated.
Case: Poor Linearity of Hot Blast Pressure
Phenomenon: During calibration, 75% error is -1.8%, and 100% signal is unstable. Analysis: Drain valve not tight, non-standard sealing gasket at pressure tapping causing micro-leakage. Treatment: Replace gasket; calibration up/down deviations meet requirements.
These cases emphasize regular inspection and standardization of spare parts. Nexisense products perform stably in blast furnace environments and support remote diagnostics.
FAQ
Why must a work permit be obtained before calibration? To ensure process isolation safety, prevent high-pressure medium leakage or electrical risks, and comply with industrial safety regulations.
What is the role of the HART communicator in calibration? It enables zero/span trim, parameter configuration, and diagnostics, far more accurate and convenient than manual adjustment.
Which calibrator should be used for low-range transmitters? Pneumatic calibrators, to avoid excessive error or contamination introduced by hydraulic types.
How to handle isolation diaphragm oil leakage? Stop using it and replace the entire sensor assembly to prevent further damage.
If the output current remains unchanged, how to troubleshoot initially? First check power supply and wiring, then verify complete process isolation, and finally inspect the amplifier board.
Possible causes of abnormally low blast furnace top pressure? Zero drift, surge protector failure, pressure tapping blockage, or poor sealing.
How to prevent water accumulation in impulse lines? Enhance insulation, drain regularly, and choose installation with appropriate slope.
What should be done after replacing the amplifier board? Perform complete zero and span calibration to ensure accuracy recovery.
Nexisense monocrystalline silicon transmitter calibration interval? Generally annually; in high-temperature, high-dust environments such as blast furnaces, six months is recommended.
What is the relationship between poor linearity and leakage? Micro-leakage causes unstable upper range; check gaskets and valve tightness.
Conclusion
The calibration procedure of monocrystalline silicon pressure transmitters emphasizes safety first and rigorous steps, achieving efficient adjustment through HART tools. Combined with troubleshooting and blast furnace diagnostic cases, it comprehensively addresses real-world challenges. With intelligent design and durability, Nexisense products support these operations, helping users reduce maintenance costs and improve system reliability.
Mastering this knowledge not only extends equipment life but also optimizes industrial processes. If you encounter specific issues when using Nexisense monocrystalline silicon pressure transmitters, it is recommended to refer to the manual or consult professional support—accurate measurement is the cornerstone of production safety.



