Key Factors Affecting Differential Pressure Transmitter Accuracy

2026-01-25

Key Factors Affecting Differential Pressure Transmitter Performance

As differential pressure transmitters rapidly evolve toward high precision and intelligence, engineers often focus on nominal accuracy (e.g., 0.075%FS or 0.1%FS) during selection, while overlooking external factors that truly determine measurement reliability in real applications. True system accuracy is not the transmitter's factory “reference accuracy” but the combined accuracy under field conditions that correctly reflects the true differential pressure. Temperature drift, static pressure effects, installation orientation, and impulse line height differences can amplify errors several times, sometimes exceeding the instrument's intrinsic accuracy by an order of magnitude.

Nexisense, a supplier specializing in industrial process sensors, with long-term service in petrochemical, power, metallurgical, and water treatment projects, systematically analyzes key factors affecting differential pressure transmitter performance based on engineering practice, and provides targeted strategies to help integrators and engineering teams effectively control errors during selection, installation, and commissioning.

pressure transmitter.png

Turndown Ratio: The “Invisible Killer” of Accuracy

Turndown ratio refers to the ratio of the maximum measurable differential pressure to the minimum, while still meeting the specified accuracy. Most smart differential pressure transmitters maintain nominal accuracy within a 10:1 turndown ratio, but accuracy usually decreases linearly or non-linearly beyond this range.

Actual impact:

  • The larger the turndown ratio (e.g., 50:1 or 100:1), the greater the zero and span errors, especially in low differential pressure ranges.

  • Some models deviate from reference accuracy at 3:1 or 2:1; different range codes have significantly varying guaranteed accuracy ranges.

Engineering countermeasures:

  1. Prefer models with turndown ratio ≥10:1 and minimal accuracy decay.

  2. Calculate required turndown ratio based on process max/min differential pressure, and ideally keep within 5:1 for optimal linearity and stability.

  3. For processes with large range variation, consider segmented measurement with multiple transmitters or smart models that support field range adjustment with minimal accuracy decay.

Temperature Variations: Dual Drift in Zero and Span

Transmitters are typically calibrated at a fixed reference temperature (20℃ or 25℃), while industrial process and ambient temperatures can fluctuate widely (-40℃ to +120℃ or higher), causing zero and span drift.

Impact patterns:

  • Near full scale (small turndown ratio), temperature impact is minor.

  • Near minimum range (large turndown ratio), temperature errors can magnify several times or even tenfold. Manuals show errors up to ~10% at 100:1 turndown ratio.

Engineering countermeasures:

  1. Use smart transmitters with built-in temperature sensors for real-time compensation.

  2. Install away from heat or cold sources; add insulation or heat sinks if necessary.

  3. For high-temperature or large ΔT applications, choose models with excellent temperature performance and perform field zero/span calibration.

pressure transmitter.png

Static Pressure Effects: The “Innate Weakness” of Capacitive Transmitters

Static pressure refers to the absolute pressure applied equally on both sides of the transmitter. In flow or level measurement, pipeline or vessel static pressure frequently varies (from atmospheric to tens of MPa), producing asymmetric forces on the diaphragm, causing zero and span drift.

Notes:

  • Capacitive transmitters are most sensitive; errors can exceed instrument accuracy at high static pressures.

  • Piezoresistive and diffused silicon types are less sensitive but still exhibit static pressure effects.

Engineering countermeasures:

  1. Check “static pressure effect coefficients” in datasheets and choose models with minimal static pressure error.

  2. Include static pressure effect in total uncertainty calculations.

  3. For high static pressure, select optimized products or perform static pressure compensation during calibration.

Installation Tilt Angle: “Gravity Error” from Fill Fluid

Filled with silicone or other fluids, a transmitter's internal measurement chamber produces additional static pressure on the diaphragm when tilted, causing output drift.

Tilt impact patterns:

  • Parallel tilt along diaphragm plane (front/back) has minimal effect.

  • Perpendicular tilt (left/right) causes significant drift; greater angle → larger drift, especially in low differential pressure.

  • Linearity remains mostly unaffected, but zero shifts noticeably.

Engineering countermeasures:

  1. Install with axis vertical (angle <3° from plumb).

  2. Left/right tilt is most sensitive; use a level during installation.

  3. For micro differential (<500Pa), tilt should be ≤1°.

pressure transmitter.png

Height Difference Between Measurement and Installation Points: Additional Hydrostatic Pressure

For maintenance or layout reasons, transmitters are often remote from pressure points via impulse lines. Height differences generate additional hydrostatic pressure, directly adding to measured differential pressure.

Error calculation:

  • Liquid: Error = ρ × g × Δh (ρ = fluid density, Δh = height difference)

  • Water: ~9.8kPa per meter; oil: larger error

  • Gas: smaller impact but density changes must be considered

Engineering countermeasures:

  1. Minimize impulse line length and height differences.

  2. For liquids, transmitter below low-pressure tap; for gases, above low-pressure tap.

  3. Use zero elevation/suppression to compensate fixed height differences in level measurement.

  4. For high-precision, use remote diaphragm seal transmitters near pressure tap.

Other Minor but Important Factors

  • Vibration and shock: causes diaphragm fatigue or poor contact; use vibration-resistant models.

  • Electromagnetic interference: caused by parallel power and signal lines; use shielded cable and single-point grounding.

  • Medium phase changes: condensation, cavitation, crystallization blocking impulse lines; use heated or purged designs.

  • Long-term stability: aging drift; regular calibration required.

FAQ: Common Questions on Differential Pressure Transmitter Accuracy

  1. How much accuracy drops at 50:1 turndown? Depends on model; zero/span errors can magnify 2-5x.

  2. Temperature change 10℃ causes how much error? Depends on product; modern smart transmitters within ±0.1%.

  3. Static pressure impact greater on capacitive or piezoresistive? Capacitive more sensitive.

  4. Installation tilt 5° causes how much error? Micro differential: 0.5-2% FS depending on range.

  5. Height difference 1m for water causes error? ~9.8kPa (~0.1 bar).

  6. How to compensate height difference? Zero elevation/suppression in transmitter or secondary instrument.

  7. Why high nominal accuracy but large field error? External factors like turndown ratio, temperature, static pressure ignored.

  8. Remote diaphragm seal eliminates height difference error? Reduces significantly but proper installation and zero adjustment still required.

  9. Vibration environment selection? Prefer high MTBF, vibration rating ≥10g.

  10. Most overlooked factor? Installation tilt and impulse line height difference.

Conclusion

Field measurement accuracy of differential pressure transmitters results from instrument precision combined with environmental and installation factors. Turndown ratio, temperature, static pressure, tilt angle, and height difference can magnify errors beyond nominal values. In practice, carefully review datasheet coefficients during selection, strictly control installation orientation and piping layout, and perform zero/span adjustment and temperature compensation during commissioning. Only by systematically considering these factors can truly reliable differential pressure measurement be achieved.