A pressure sensor can have an operating temperature range that differs from its compensated temperature range. For engineering companies and OEM buyers, confusing these entries can leave the measurement acceptable as equipment but unsuitable for the required pressure uncertainty. A procurement review must connect the temperature at each part of the assembly with the applicable specification.
Use this guide to distinguish operating conditions, temperature compensation and temperature-related output changes. It is a specification review, not a claim that every Nexisense model has the same limits or that a published operating range guarantees unchanged measurement accuracy throughout that range.

Application Requirements for System Integrators
Outdoor monitoring projects may experience temperature changes at the enclosure, cable termination and process connection at different times. Record the expected minimum and maximum conditions, exposure duration and installation arrangement. Ambient weather data alone does not establish the temperature experienced by every sensor component.
For an OEM machine with warm process fluid, the instrument connection may conduct heat into the assembly even when the control cabinet is cool. Give the supplier the process and ambient conditions separately. Any proposed stand-off, tubing or thermal accessory needs a documented application review rather than an assumed temperature reduction.
Nexisense Product Reference
Nexisense FST100-1002 publishes an operating temperature of -40 to +85 C and a temperature compensation range of -20 to +85 C. YF-P1101 separately publishes an operating temperature of -40 to +125 C and temperature coefficient entries. These references belong to different products and must not be combined into a single improved specification.
Product specification (English): FST100-1002
Product Parameters and Procurement Checks
| Parameter | Published Reference | Engineering Check |
|---|---|---|
| FST100-1002 operating temperature | -40 to +85 C | Check the intended installation and all accessory limits. |
| FST100-1002 temperature compensation | -20 to +85 C | Do not infer the same measurement behaviour below this range. |
| YF-P1101 operating temperature | -40 to +125 C | Confirm how process and ambient limits apply to the order. |
| YF-P1101 zero temperature coefficient | Typical +/-0.03% FS/C; maximum +/-0.05% FS/C | Clarify reference temperature and applicable calculation conditions. |
| YF-P1101 sensitivity temperature coefficient | Typical +/-0.03% FS/C; maximum +/-0.05% FS/C | Assess separately from the basic accuracy grade. |
Selection Guide
Write a temperature schedule for normal operation, startup, cleaning, shutdown and storage where relevant. Identify the required measurement performance in each state. A condition during which the instrument is not required to measure still needs a supplier-confirmed equipment limit; storage and operating entries are not interchangeable permissions.
Ask how the quoted accuracy, compensation and temperature coefficients are defined. Check whether an overall error statement already includes a temperature contribution before adding the same effect again. Where a public page does not state the conditions needed for a reliable calculation, obtain written clarification instead of inventing a combined worst-case figure.

Integration, Installation and Commissioning
Keep sensor temperature considerations separate from controller scaling. Changing a PLC span or applying a constant offset is not a general correction for temperature-dependent behaviour. Record any approved compensation method, its input data and the circumstances under which it is valid, and retain the unmodified measurement where the project requires traceability.
Plan verification at representative conditions when temperature is important to the acceptance requirement. Record the reference instrument, stabilization criteria and actual temperatures used. Installation work must follow the approved procedure, including process isolation where needed. Do not expose a sensor to an unverified condition merely to test whether it survives.
Illustrative Project Application
Illustrative engineering example: a remote equipment supplier compares the required cold-start measurement condition with a proposed sensor compensation range. The buyer requests clarification for the uncovered condition and revises the acceptance plan before ordering. No field trial result, guaranteed thermal correction or customer installation is implied.

Why Consider Nexisense
Nexisense provides model-specific temperature entries that support a more precise technical discussion. Send the temperature schedule, medium, connection arrangement and allowable pressure deviation with the enquiry. Ask for the ordered assembly limits, including cable and connector conditions, rather than relying on the sensing element reference alone.
Frequently Asked Questions
Q1. What is the difference between operating and compensated range?
They are separate specification entries. The operating range describes stated operating conditions, while compensation information relates to measurement behaviour. Confirm the exact supplier definitions for the proposed configuration.
Q2. Can an operating limit be used as an accuracy guarantee?
Not by itself. Review the accuracy definition, temperature compensation and coefficients together, including the conditions and limitations attached to each entry.
Q3. Are process temperature and ambient temperature identical?
No. Describe both in the application schedule and ask how the assembly limits apply. Do not assume that one published temperature entry resolves every installation condition.
Q4. Should typical coefficients be used for acceptance?
Use the value and conditions agreed in the purchase specification. A typical reference is not automatically a contractual maximum for every delivered instrument.
Q5. Can a PLC offset remove every temperature effect?
No general guarantee follows from a constant offset. Any correction must be justified for the application and verified under the conditions for which it is intended.
Q6. Are storage limits valid during measurement?
Do not substitute storage limits for operating conditions. Specify whether the instrument is powered, pressurized or required to measure, and obtain the applicable supplier limits.
Q7. Do cable and connector limits also need review?
Yes. Review the ordered assembly, termination environment and accessories. A temperature entry for one component does not automatically establish the limit of the complete installation.
Q8. What evidence helps an OEM close a temperature enquiry?
Provide the duty schedule, installation arrangement and uncertainty requirement. Retain the supplier clarification and agreed verification conditions with the order and commissioning records.
Summary
Treat operating temperature, compensation and temperature coefficients as distinct purchasing inputs. Identify the required measurement conditions, obtain missing definitions and verify the complete assembly rather than extending a catalogue limit beyond its stated scope.