A correct 4-20 mA scaling formula cannot compensate for an underpowered transmitter loop. Integrators need enough supply voltage at the field device after cable resistance, analogue input burden and other series components are included. Problems often appear near the high end of the current range rather than at the initial zero check.
This guide focuses on the electrical power budget for two-wire pressure measurement loops. It is intended for panel builders, engineering contractors and OEM control teams specifying Nexisense pressure transmitters. It complements signal scaling work but does not replace the device wiring diagram or any required electrical safety assessment.

Application Requirements for System Integrators
Typical projects include remote pump stations, packaged process skids and distributed PLC panels. The equipment designer should identify whether the input is active or passive and which component actually supplies loop power. Connecting two power sources or selecting a passive input without an external supply can prevent correct operation.
Draw the whole current path, including test terminals, isolators, surge protection and barriers. Some components have a near-constant voltage drop rather than a simple resistance. Use the component documentation instead of forcing every burden into a single resistor approximation.
Nexisense Product Reference
The Nexisense YF-P1101 reference lists a two-wire current output and a published load relationship: R <= (Vs - 7.5 V) / 0.02 A. The same page lists alternative voltage outputs and supply ranges; those alternatives are not interchangeable wiring instructions. Confirm the supply specification and terminal assignment for the selected current-output order.
Product specification (English): YF-P1101
Product Parameters and Procurement Checks
| Parameter | Published Reference | Engineering Check |
|---|---|---|
| YF-P1101 current output | 4-20 mA, two-wire option | Confirm passive or active PLC input arrangements. |
| Published load relationship | R <= (Vs - 7.5 V) / 0.02 A | Use the ordered variant specification and minimum available supply. |
| Published supply entries | 9-32 V DC; 5-30 V DC | The page lists variants; obtain the applicable output-to-supply mapping. |
| Current consumption entry | Maximum 25 mA for two-wire system | Check power supply sizing and documented abnormal-current requirements. |
| Voltage output alternative | 0-10 V; 0-5 V | Do not apply the two-wire current load formula to a voltage input. |
Selection Guide
Calculate against the minimum voltage that the panel supply can deliver under the specified conditions, not its nominal label alone. Add round-trip cable resistance at the expected installation conditions and include every series burden. Leave an explicit design margin rather than selecting a loop that only meets the theoretical equality.
Illustrative calculation: at 24 V and using the published 20 mA load relationship, the calculated ceiling is 825 ohms. This is a calculation example, not a universal recommended load. A lower supply, series voltage drops or a different required operating condition reduces the available headroom.

Integration, Installation and Commissioning
For fixed voltage drops, subtract those drops before evaluating the resistance available to the remaining loop. Confirm that any isolator passes the intended signal and provides the required supply capability. Do not assume a compatible analogue signal automatically means a compatible power arrangement.
During commissioning, measure current and the transmitter terminal voltage at representative low and high outputs. A good reading at the lower endpoint does not prove adequate voltage at the upper endpoint. Use designated test points and an approved procedure to avoid interrupting a live control function.
Document the final cable length, input burden, supply setting and field-device configuration in the loop drawing. If the cable is extended or a barrier is added later, rerun the budget. Investigate grounding and interference separately; increasing supply voltage is not a general cure for noisy measurements.
Illustrative Project Application
Illustrative engineering example: a contractor adds an isolator to a long pressure transmitter circuit. The signal checks correctly near its lower endpoint but becomes limited as current rises. The team recalculates the complete voltage budget and checks transmitter terminal voltage before changing any calibration. No customer outcome or guaranteed corrective setting is claimed.

Why Consider Nexisense
The YF-P1101 public specification provides an explicit load relationship that supports a traceable enquiry. Ask Nexisense to confirm the ordered wiring, minimum terminal voltage and applicable supply range alongside the required pressure calibration. That information makes panel design review more useful than choosing a transmitter only by its nominal output signal.
Frequently Asked Questions
Q1. What does the loop power budget include?
Include the transmitter voltage requirement, cable losses, PLC input burden and documented drops across every series component.
Q2. Is nominal 24 V enough information?
No. Use the minimum supply available under the required conditions, including tolerance and any upstream drops.
Q3. Is the 825 ohm example a recommended resistor?
No. It is an illustrative ceiling from the published formula at a stated supply. The actual design needs its own component data and margin.
Q4. Can a voltage-output transmitter use the same formula?
No. Voltage-output wiring and load requirements differ from a two-wire current loop. Use the applicable variant documentation.
Q5. Why can a loop work at low current but fail at high current?
Resistive voltage drops increase with current. Available terminal voltage may become inadequate near the upper part of the signal range.
Q6. Should a barrier be represented as resistance?
Only when its documentation supports that model. Some barriers or isolators require a separate voltage-drop treatment.
Q7. Does a pressure calibration fix an electrical supply problem?
No. Verify the electrical loop first; otherwise calibration changes can hide a symptom without correcting the cause.
Q8. What should the purchase order identify?
Specify the output variant, supply arrangement, pressure range, connector, wiring drawing and any required loop interface documentation.
Summary
Evaluate the pressure transmitter and PLC input as one electrical circuit. A documented minimum-voltage budget, verified wiring and high-current terminal-voltage check help distinguish power limitations from calibration or process problems before the equipment is handed over.